ECOLINE TANDEM P - 44DESP-14(P)

Bitzer ecoline tandem P 44DESP-14(P)

ECOLINE TANDEM P - 44DESP-14(P)

Tandem compressors are the simplest way of connecting two compressors in parallel. Turning on and shutting off one compressor allows for a particularly effective graduation of output. The 4- and 6-cylinder models can also be equipped with capacity control systems (cylinder cutoff), allowing them to run with up to four or six levels of output.

Displacement No. of cylinder x bore x stroke Weight Max. pressure (LP/HP) Connection suction line Connection discharge line Oil type R290/R1270
1450 RPM 50Hz 1750 RPM 60Hz
SI 53,7 m3/h 64,8 m3/h 4+4 x 50 mm x 39,3 mm 180 kg 19 / 32 bar 35 mm - 1 3/8'' 2x22 mm - 7/8'' SHC226E (Standard)
IP 1895.6 CFH 2287.6 CFH 4+4 1.97 inch x 1.55 inch 397 lb 275 / 464 psi 35 mm - 1 3/8'' 2x22 mm - 7/8'' SHC226E (Standard)

Extent of delivery (Standard)

Type Motor protection Enclosure class Vibration dampers Oil charge
SI SE-B2 IP66 Standard 4,50 dm³
IP SE-B2 IP66 Standard 158.4 fl oz

Available Options

Type Discharge gas temperature sensor Start unloading Capacity control Capacity Control - infinite Additional fan Refrigerant Injection (RI) Crankcase heater
SI Option Option 100-75-50-25% (Option) 100-10% (Option) Option Option 2 x 0..120 W PTC (Option)
IP Option Option 100-75-50-25% (Option) 100-10% (Option) Option Option 2 x 0..120 W PTC (Option)

Motor data

Type Motor version Motor voltage (more on request) Max operating current Starting current (Rotor locked)
SI 1 380-420V PW-3-50Hz 2x16.5 A 2x82.4 A
IP 1 440-480V PW-3-60Hz 2x16.5 A 2x82.4 A

Sound measurement

Type Sound power level Sound pressure level @ 1m
(+5°C / 50°C) (-10°C / 45°C) (-35°C / 40°C) (+5°C / 50°C) (-10°C / 45°C) (-35°C / 40°C)
SI 73,7dB(A) @ 50Hz 76,6dB(A) @ 50Hz 77,5dB(A) @ 50Hz 65,7dB(A) @ 50Hz 68,6dB(A) @ 50Hz 69,5dB(A) @ 50Hz
IP 76,2dB(A) @ 60Hz 78,1dB(A) @ 60Hz 80dB(A) @ 60Hz 68,2dB(A) @ 60Hz 70,1dB(A) @ 60Hz 72dB(A) @ 60Hz