ECOLINE TANDEM P - 44NESP-40(P)

Bitzer ecoline tandem P 44NESP-40(P)

ECOLINE TANDEM P - 44NESP-40(P)

Tandem compressors are the simplest way of connecting two compressors in parallel. Turning on and shutting off one compressor allows for a particularly effective graduation of output. The 4- and 6-cylinder models can also be equipped with capacity control systems (cylinder cutoff), allowing them to run with up to four or six levels of output.

Displacement No. of cylinder x bore x stroke Weight Max. pressure (LP/HP) Connection suction line Connection discharge line Oil type R290/R1270
1450 RPM 50Hz 1750 RPM 60Hz
SI 112,5 m3/h 135,8 m3/h 4+4 x 70 mm x 42 mm 308 kg 19 / 32 bar 54 mm - 2 1/8'' 2x28 mm - 1 1/8'' SHC226E (Standard)
IP 3973 CFH 4795 CFH 4+4 x 2.76 inch x 1.65 inch 586 lb 275 / 464 psi 54 mm - 2 1/8'' 2x28 mm - 1 1/8'' SHC226E (Standard)

Extent of delivery (Standard)

Type Motor protection Enclosure class Vibration dampers Oil charge
SI SE-B2 IP66 Standard 6,10 dm³
IP SE-B2 IP66 Standard 215 fl oz

Available Options

Type Discharge gas temperature sensor Start unloading Capacity control Capacity Control - infinite Additional fan Oil service valve Crankcase heater
SI Option Option 100-75-50-25% (Option) 100-10% (Option) Option Option 2 x 0..140 W PTC (Option)
IP Option Option 100-75-50-25% (Option) 100-10% (Option) Option Option 2 x 0..140 W PTC (Option)

Motor data

Type Motor version Motor voltage (more on request) Max operating current Starting current (Rotor locked)
SI 1 380-420V PW-3-50Hz 2x33.2 A 2x97.0 A Y / 2x158.0 A YY
IP 1 440-480V PW-3-60Hz 2x33.2 A 2x97.0 A Y / 2x158.0 A YY

Sound measurement

Type Sound power level Sound pressure level @ 1m
(+5°C / 50°C) (-10°C / 45°C) -35°C / 40°C (+5°C / 50°C) (-10°C / 45°C) -35°C / 40°C
SI 81,0 dB(A) @ 50Hz 81,5 dB(A) @ 50Hz (86,0) dB(A) @ 50Hz 73,0 dB(A) @ 50Hz 73,5 dB(A) @ 50Hz (78,0) dB(A) @ 50Hz
IP 83,5 dB(A) @ 60Hz 84,0 dB(A) @ 60Hz (88,5) dB(A) @ 60Hz 75,5 dB(A) @ 60Hz 76,0 dB(A) @ 60Hz (80,5) dB(A) @ 60Hz