BITZER ECOLINE VARISPEED R404A/R507A - 4CE-6.F1Y

Bitzer Semi-hermetic frequency-controlled ecoline varispeed 4CE-6.F1Y

ECOLINE VARISPEED R132A - 4CE-6.F1Y

With their groundbreaking properties, the BITZER ECOLINE compressors are complemented by the new series with integrated frequency inverters (FI), allowing for seamless capacity control. Seamless capacity control minimizes suction pressure fluctuations and cycling rates, thus reducing energy costs. In particular, single-compressor applications can be completed with a considerably higher system efficiency.

  • Displacement at 87 Hz : 57,4
  • Number of cylinders : 4
  • Oilcharge : 2,0 dm3

Frequency 30 Hz

Compressor type Cond.temp. Qo / Pe Evaporating temperature °C
[°C] 5 0 -5 -10 -15 -20 -25 -30 -35 -40
4CE-9.F3Y 30 Qo 22000 18360 15220 12510 10180 8190 6490 5050 3850 2850
Pe 4,18 4,14 4,03 3,85 3,62 3,35 3,05 2,74 2,41 2,09
40 Qo 18860 15700 12970 10610 8590 6860 5390 4150 3120 2280
Pe 5,12 4,95 4,71 4,41 4,08 3,71 3,33 2,94 2,55 2,17
50 Qo 15670 13010 10710 8720 7010 5560 4320 3290 2440 1740
Pe 5,97 5,66 5,30 4,89 4,46 4,01 3,55 3,09 2,64 2,22

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]

Frequency 50 Hz

Compressor type Cond.temp. Qo / Pe Evaporating temperature °C
[°C] 5 0 -5 -10 -15 -20 -25 -30 -35 -40
4CE-9.F3Y 30 Qo 38000 31750 26300 21650 17610 14160 11220 8730 6650 4930
Pe 7,47 7,37 7,13 6,78 6,32 5,80 5,21 4,60 3,97 3,35
40 Qo 32600 27150 22400 18350 14850 11850 9310 7180 5400 3930
Pe 9,10 8,73 8,25 7,67 7,02 6,31 5,57 4,81 4,07 3,35
50 Qo 27100 22500 18520 15080 12120 9610 7480 5690 4220 3010
Pe 10,50 9,89 9,18 8,39 7,55 6,68 5,79 4,91 4,07 3,28

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]

Frequency 70 Hz

Compressor type Cond.temp. Qo / Pe Evaporating temperature °C
[°C] 5 0 -5 -10 -15 -20 -25 -30 -35 -40
4CE-9.F3Y 30 Qo 52800 44050 36550 30050 24450 19660 15580 12130 9240 6840
Pe 10,79 10,63 10,27 9,73 9,06 8,27 7,40 6,48 5,55 4,63
40 Qo 45250 37700 31150 25500 20600 16460 12930 9970 7500 5460
Pe 13,11 12,56 11,84 10,97 9,99 8,94 7,83 6,71 5,61 4,56
50 Qo 37600 31250 25700 20950 16840 13340 10380 7910 5860 4180
Pe 15,08 14,17 13,10 11,93 10,68 9,38 8,07 6,77 5,53 4,37

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]

Frequency 87 Hz

Compressor type Cond.temp. Qo / Pe Evaporating temperature °C
[°C] 5 0 -5 -10 -15 -20 -25 -30 -35 -40
4CE-9.F3Y 30 Qo 64000 53400 44300 36400 29650 23800 18880 14700 11200 8300
Pe 13,76 13,55 13,07 12,38 11,50 10,47 9,35 8,16 6,96 5,77
40 Qo 54900 45700 37750 30900 25000 19960 15680 12080 9090 6620
Pe 16,69 15,98 15,04 13,92 12,65 11,29 9,86 8,42 7,00 5,64
50 Qo 45600 37900 31200 25400 20400 16170 12590 9580 7100 5070
Pe 19,18 17,98 16,61 15,09 13,48 11,80 10,11 8,44 6,84 5,35

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]

Compressor type Motor version Displacement at 87 Hz Number of cylinders Oil charge Weight Pipe connections FI connection Max. operating current Max. power consumption
DL SL
m3/h dm3 kg mm pouce mm pouce Volt Amp kW
4CE-6.F1Y 2 57,4 4 2,0 106 22 7/8 35 13/8 380..480 V/3/50 Hz➂
380..480 V/3/60 Hz➂
22 12