LHE series with 2nd generation 2-stage - LH124E/S4G-12.2(Y)

LHE series with 2 stage - LH124E/S4G-12.2(Y)

LHE 2nd generation 2-stage - LH124E/S4G-12.2(Y)

The components of the air cooled condensing units with double stage compressors of the .2 Generation have a compact design and boast coordinated components such as efficient EC fans and system-optimised condensing heat exchangers (mini-channel) in low temperature applications. The condensing units also feature a robust design, facilitating a whole host of applications with a large capacity range. They conform with the Ecodesign Directive and can also be used with low-GWP refrigerants, making them future-proof.

  • Speed-controlled EC fans --> for energy-saving and low noise operation
  • System-optimised mini-channel condensing heat exchanger for high heat transfer rates and small refrigerant charge
  • Conforms with Ecodesign
  • Available for numerous refrigerants/including refrigerants with low GWP
  • Robust design and compact dimensions
Type Displacement (1450 RPM 50Hz) Displacement (1750 RPM 50Hz) Weight Total width Total depth Total height Connection suction line Connection liquid line Fans: Number
SI 42.30 / 27.00 m³/h 51.05 / 32.59 m³/h 348 kg 1591 mm 1000 mm 848 mm 35 mm - 1 3/8'' 22 mm - 7/8'' 2
IP 1494 / 953 CFH 1803 / 1151 CFH 767 lb 54'' 34'' 28,8'' 35 mm - 1 3/8'' 22 mm - 7/8'' 2
Type Voltage (50Hz, more on request) Current / Power consumption of each fan (50Hz) Air flow condenser 50Hz Voltage (60Hz, more on request) Current / Power consumption of each fan (60Hz) Air flow condenser 60Hz Coil Volume Receiver type (Standard)
SI 230V-1-50Hz (Standard) 2,1 A / 330 W 9800 m³/h 230V-1-60Hz (Standard) 2,1 A / 330 W 9800 m³/h 2,6 dm3 F302H
IP 230V-1-50Hz (Standard) 2,1 A / 330 W 5772 CFM 230V-1-60Hz (Standard) 2,1 A / 330 W 5772 CFM 91,52 fl oz F302H
Type R22 R404A/R507A R448A R449A
SI 32,7 kg 28,8 kg 30,1 kg 30,2 kg
IP 72.2 lb 63.7 lb 66.4 lb 66.7 lb

Available Options

Type Oil separator Check valve High & low pressure switch Liquid sub cooler (also mounted)
SI Option Option Option Option
SI Option Option Option Option