Open 2nd generation - 4G.2(Y)

Bitzer open 2nd generation 4G.2(Y)

2nd Generation - 4G.2(Y)

With the 2nd generation, BITZER has taken a decisive step forward: There is now a model range for chlorine-free HFC refrigerants and HFCKW. Thanks to their highly efficient and robust designs, the standard compressors meet all the criteria for operation with chlorinated and chlorine-free refrigerants.

  • Suitable for coupling and belt drives.
  • Pressure oil lubrication with reversible gear pump.
  • The special oil return system results in extremely low oil carry over.
Displacement No. of cylinder x bore x stroke Allowed speed range Weight Max. pressure (LP/MP/HP) Connection suction line Connection discharge line Oil type R134a/R407C/R404A/R507A/R407A/R407F Oil type R22 (R12/R502)
1450 RPM 50Hz 1750 RPM 60Hz
SI 84,5 m3/h 102,0 m3/h 4 x 75 mm x 55 mm 750 .. 1750 1/min 129 kg 19 / 25 bar 42 mm - 1 5/8'' 28 mm - 1 1/8'' tc<55°C: BSE32 / tc>55°C: BSE55 (Option) B5.2 (Standard)
IP 2984,1 CFH 3602,1 CFH 4 x 75 mm x 55 mm 750 .. 1750 rpm 284,4 lb 275 / 363 psi 42 mm - 1 5/8'' 28 mm - 1 1/8'' tc<55°C: BSE32 / tc>55°C: BSE55 (Option) B5.2 (Standard)

Extent of delivery (Standard)

Type Oil charge Protective charge Suction shut-off valve Discharge shut-off valve Pressure relief valve
SI 4,7 dm3 Standard Standard Standard Standard
IP 165,4 fl oz Standard Standard Standard Standard

Available Options

Type Coupling (..-K) w. A/C + medium Coupling (..-K) w. low temp. Coupling housing Motor pulley (..-S) V-belts Discharge gas temperature sensor Start unloading Connection cooling water Capacity control Additional fan Water-cooled cylinder heads Oil service valve Crankcase heater Oil pressure monitoring Kit for marine application
SI KK620 [<22kW] / KK630 [<45kW] (Option) KK625 [<22kW] / KK630 [<45kW] (Option) Option 190, 210, 230 mm (Option) 5 x SPA (Option) Option (incl. INT69VS) Option R 3/4'' (Option) 100-50% (Option) Option Option Option 140 W (Option) MP54 (Option) Option
IP KK620 [<22kW] / KK630 [<45kW] (Option) KK625 [<22kW] / KK630 [<45kW] (Option) Option 190, 210, 230 mm (Option) R 3/4'' (Option) Option (incl. INT69VS) Option R 1/2'' (Option) 100-50% (Option) Option Option Option 140 W (Option) MP54 (Option) Option