Scroll Compressors ESH Tandem - ESH725(B)Y + ESH736(B)Y

Bitzer scroll compressor ESH Tandem - ESH725(B)Y + ESH736(B)Y

Scroll compressor ESH Tandem - ESH725(B)Y + ESH736(B)Y

BITZER offers kits for tandem units for parallel operations. They consist of two compressors connected in parallel and provide significant benefits over individual compressors with the same output. The compound compressor units are distinguished by groundbreaking technical features, extraordinarily high energy efficiency and reliability.

  • Efficient capacity control through pairs of compressors with equal and unequal displacements
  • Optimised pressure and suction pipe arrangement in combined compressor unit
  • Reliable oil and gas equalisation
  • Solid frame construction for low vibration levels
  • Compressor with Rotalock or direct brazing connections
  • Suitable for the refrigerants R134a, R407C, R404A, R507A and R22

With R134a (Polyolester oil BSE35K required.)

Compressor type Cond.temp. Qo / Pe Saturated suction temperature °C
[°C] 12,5 10 7,5 5 0 -5 -10 -15
ESH725(B)Y
+
ESH736(B)Y
30 Qo 61100 55800 51000 46500 38400 31500 25600 20550
Pe 7,67 7,59 7,52 7,46 7,38 7,32 7,29 7,27
40 Qo 55100 50400 45950 41850 34550 28300 22900 18320
Pe 9,37 9,34 9,31 9,27 9,19 9,12 9,07 9,04
50 Qo 48950 44700 40800 37150 30600 25000 20150 16080
Pe 11,56 11,54 11,51 11,48 11,39 11,33 11,33 11,43

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]


With R407C (Polyolester oil BSE35K required.)

Compressor type Cond.temp. Qo / Pe Saturated suction temperature °C
[°C] 12,5 10 7,5 5 0 -5 -10 -15
ESH725(B)Y
+
ESH736(B)Y
30 Qo 89300 81800 74800 68300 56700 46700 38200 30900
Pe 10,24 10,19 10,17 10,15 10,16 10,18 10,20 10,18
40 Qo 79900 73100 66800 61000 50500 41500 33800
Pe 13,02 13,01 13,01 13,01 13,04 13,05 13,02
50 Qo 70100 64200 58600 53400 44100 36100
Pe 16,67 16,68 16,68 16,68 16,67 16,59

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]

Saturated suction and discharge temperatures are based on dew point temperatures (according to EN 12900).


With R404A / R507A (Polyolester oil BSE35K required.)

Compressor type Cond.temp. Qo / Pe Saturated suction temperature °C
[°C] 12,5 10 7,5 5 0 -5 -10 -15
ESH725(B)Y
+
ESH736(B)Y
30 Qo 76000 64100 53800 44850 37100
Pe 12,19 12,25 12,26 12,22 12,15
40 Qo 71700 66000 55700 46700 38900 32150
Pe 15,48 15,49 15,50 15,46 15,41 15,33
50 Qo 60500 55700 47050 39450 32800 27050
Pe 19,50 19,48 19,44 19,38 19,30 19,22

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]

Data are valid for R404A. Slight variations have to be considered for R507A


With R22

Compressor type Cond.temp. Qo / Pe Saturated suction temperature °C
[°C] 12,5 10 7,5 5 0 -5 -10 -15
ESH725(B)Y
+
ESH736(B)Y
30 Qo 87800 80900 74500 68500 57700 48350 40100 33000
Pe 10,86 10,80 10,76 10,74 10,74 10,77 10,81 10,84
40 Qo 79700 73400 67600 62100 52200 43550 35950
Pe 13,54 13,53 13,53 13,53 13,56 13,60 13,61
50 Qo 71500 65900 60600 55600 46600 38650
Pe 16,83 16,84 16,86 16,87 16,89 16,88

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]

Compressor type Dis place-ment 50 Hz Oil charge Weight Pipe connections Motor Electrical Data Assembly kit no.
Discharge line (DL) Suction line (SL) max. workingcurrent max. power con-sumption Starting currentRLA Rotalock version Version "B"
m3/h dm3 kg mm inch mm inch Amp kW Amp
ESH725(B)Y
+
ESH736(B)Y
61 8,0 184 28 1 1/8 42 1 5/8 380..420 V/3/50 Hz
440..480 V/3/60 Hz
17 + 24,5 9,8 + 14,2 95 + 134 35810501 35810601