BITZER 2nd generation 2-stage R22

Bitzer Semi hermetic 2-stage S6F-30.2Y

Semi hermetic 2-stage R22 - S6F-30.2Y

BITZER is raising the bar in terms of technology and capacity for expanded low temperature applications with the 2nd generation of 2-stage compressors. This series is the result of extensive research on the basis of years of experience in the construction of highly efficient and solid reciprocating compressors. The gas flow control and working valves are specially adapted for low temperature applications.

  • Displacement at 1450 min-1 : 101,1 (LP) 50,5 (HP)
  • Number of cylinders : 6
  • Oilcharge : 4,75 dm3

With liquid subcooling 50Hz (R22)

Compressor type Cond.temp. Qo / Pe Evaporating temperature °C
[°C] -20 -25 -30 -35 -40 -45 -50
S6F-30.2Y 30 Qo 48800 40750 33700 27400 21900 17030 12610
Pe 21,23 19,52 17,78 16,04 14,30 12,57 10,86
35 Qo 48250 40350 33350 27150 21650 16710 12200
Pe 22,71 20,83 18,95 17,06 15,18 13,31 11,45
40 Qo 47750 39950 33000 26850 21350 16390 11790
Pe 24,18 22,15 20,11 18,07 16,03 13,99 11,96
45 Qo 47250 39550 32700 26600 21100 16100
Pe 25,66 23,45 21,25 19,05 16,84 14,60
50 Qo 46750 39200 32450 26400 20900
Pe 27,12 24,73 22,37 20,01 17,59
55 Qo 46300 38850 32200 26200
Pe 28,56 25,99 23,47 20,92

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]

Without liquid subcooling 50Hz (R22)

Compressor type Cond.temp. Qo / Pe Evaporating temperature °C
[°C] -20 -25 -30 -35 -40 -45 -50
S6F-30.2Y 30 Qo 44450 36250 29200 23200 18060 13650 9820
Pe 17,41 16,43 15,32 14,06 12,63 11,02 9,20
35 Qo 42700 34800 28050 22250 17280 12980 9220
Pe 18,91 17,74 16,44 14,99 13,37 11,56 9,56
40 Qo 40900 33350 26900 21300 16510 12330 8630
Pe 20,40 19,09 17,61 15,96 14,12 12,07 9,82
45 Qo 39100 31900 25700 20400 15760 11700
Pe 21,87 20,44 18,80 16,95 14,85 12,50
50 Qo 37250 30400 24600 19490 15040
Pe 23,31 21,79 20,02 17,96 15,57
55 Qo 35450 29050 23500 18610
Pe 24,71 23,11 21,23 18,97

Qo - Cooling capacity [Watt], Pe - Power consumption [kW]

Compressor type Displacement at 1450 min-1 Number of cylinders Oil charge Weight Pipe connections Motor Max. operating current Max. power consumption Starting current(lockedrotor)
LP HP DL SL
dm3 Kg mm pouce mm pouce Amp kW Amp. Y/YY
S6F-30.2Y 101,1 50,5 6 7.75 234 35 13/8 42
54
15/8
21/8
380 ..420YY/3/50
440 ..480 YY/3/60
51 31,9 135/220